This site uses cookies for functional purposes. To continue please read and agree to our Data Privacy.

By closing this message, you consent to our use of cookies on this device.

  1. Jarkko Aho
  2. PLCnext Technology & PLCnext Controls
  3. Tuesday, 29 January 2019
  4.  Subscribe via email

Hey Community

We had a working AXC F 2152 controller that was used for different demos and tests, and decided to give it a Type 2 reset from AXC F 2152 English manual page 33.

After the reset the controller flashed the boot and D lights a couple of times and after that it went completely dark. The controller will not respond even if power is reconnected or reset is pressed again. Has anyone else tried the Type 2 reset and had this problem or was this controller just faulty?

The SD-card that was inside the controller booted and worked fine in other controllers after the reset and other SD-cards did nothing in the faulty controller.

Attachments (1)
Accepted Answer
Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

OK, if none of the reset procedures work, then I'm afraid that there's not much choice but to return the PLC to Phoenix Contact through your local subsidiary.

- Martin.

Phoenix Contact Electronics Headquarters - Support Center

Martin PLCnext Team Accepted Answer Pending Moderation
0
Votes
Undo

Hello Jarkko,

Can you tell me what version of firmware you have on the controller?

For firmware version 1.2, the complete Type 2 reset procedure is slightly different to the procedure described in the User Manual - the details are in the change notes for firmware version 1.20.

30 01 2019 07 29 35

Can you please try this reset procedure and let us know the result?

- Martin

Phoenix Contact Electronics Headquarters - Support Center

Jarkko Aho Accepted Answer Pending Moderation
0
Votes
Undo

There is no way to check the firmware now. We don't have any access in the controllers online diagnostics, because it won't start.

But I'm pretty sure it was fw 1.1.0.23 like most of our controllers.

Right now I only have one free demo controller and I rather not risk to kill it too. I will return to this matter after I have controllers to spare.

- Jarkko

emilg Accepted Answer Pending Moderation
1
Votes
Undo

Here is from the data sheet of the adapt module:

NOTE: Device defect due to
impermissible firmware version
The Inline adapter terminal is designed to be
aligned to the right of PLCnext controllers with
specific firmware versions. If you align the
Inline adapter terminal next to a PLCnext
controller with a firmware version that is not
permitted, this can cause a device defect to
the PLCnext controller.
Make sure that the Inline adapter terminal is
only aligned next to a PLCnext controller with
a firmware version that is permitted.
AXC F ... PLCnext controllers with the
following firmware versions are permitted:
– AXC F 2152 with firmware Version  1.2test

Attachments (1)
Jarkko Aho Accepted Answer Pending Moderation
0
Votes
Undo

The adapt module was in the picture, just to show that the controller had power connected. It was the first module I had in hand to get a picture how controller was completely dark.

- Jarkko

  • Page :
  • 1


There are no replies made for this post yet.
However, you are not allowed to reply to this post.

We have 47 guests and 2 members online